Permit Number: T10CM03312
Parcel: 128070530

Address:
6131 E 17TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03312
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T10CM03312 Rev 1/11/11
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

STRUCTURAL PLANS:

1. Show a beam size and species with appropriate load carrying capacity for existing and proposed roof loads at the 16' opening, R301.1. The 6x10 beam is undersized and cannot be checked without knowing the amount of both new and existing roof being supported by this beam. Show the distance from the beam to the existing interior load bearing walls for determining existing roof load supported by the 6" x 10" beam. Show the beam rating (DF #1 or #2).

SECTIONS - DETAILS:

1. Specify a #15 water-resistive barrier between studs and hardy board sheathing, R703.2. Add notation to the Wall Section sheet #4.

PLUMBING PLANS:

1. Show the replacement of ¾" water pipe with 1" pipe on the plan between the meter and shut off valve.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/12/2011 SUE REEVES REJECT SHELF Completed