Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM03308
Parcel: 113100010

Address:
1545 E COPPER ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03308
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM03308
1545 E Copper St
Salpointe High School,
23.5 KW Photovoltaic Systems

The electrical plans have been denied for the following:

1. The attached Panel Schedule for Pnl AC 7 is too light, unable to clearly read, and it will not come through when copied for records.
2. The Bus rating on the panel (AC-7) appears to read as 600 Amps not the 150 Amps as designated on the Equipment Schedule. Once the determination is made on the ampacity of the panel show how it complies with NEC 690.63.(B).2, notate on plan.
3. Sheet 3006-06 Rev B appears to conflict with Sheet 3006-10 Rev 10 in that the flow from the Aggregation Center to the PV Meter to the AC Disconnect do not follow the same path, both diagrams need to follow the same flow.
4. NEC 690.14.(D).2, requires that the AC Disconnect be mounted with- in sight of the inverters, drawing shows on the other side of the wall ?
5. Notate on plan that installer is to provide Warning and
Identification signs as per the following sections, NEC 690-
14.(C).2....... 14.(D).4....... 17....... and 53.

Ray T Majuta,
PDSD,City of Tucson,
Elect Pln Ck,
12/06/10
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/16/2010 CPIERCE1 OUT TO CUSTOMER Completed
12/16/2010 SUE REEVES REJECT SHELF Completed