Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM03284
Parcel: 12215120A

Address:
3120 E LESTER ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03284
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2011 GERRY KOZIOL WWM REVIEW Approved
03/23/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T10CM03284
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:

" Provide manufacturer specification sheets for the collector panels showing suitable for connection to utility grid. The KC120-1 is rated for off-grid use.


If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
04/05/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET RS1: THIS SHEET HAS BEEN ADDED TO THE ORIGINAL REVIEW SET. PROVIDE STRUCTURAL CALCULATIONS SEALED, SIGNED, AND DATED BY MICHAEL E. HARRIS FOR THE RAMADA FRAMING AND FOUNDATION.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
04/14/2011 SUE REEVES REJECT SHELF Completed