Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T10CM03263
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/22/2010 | RONALD BROWN | ADA | REVIEW | Passed | |
| 11/24/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/03/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | Please clarify who is to build the demising wall. This is not clear on the plans. Sheet D1-0b sort of indicates it's a new wall between remittal space and new Old Navy space. Sheet A1-0 indicates that's it's existing. Please reconcile and reference the detail shown on the drawings. |
| 12/03/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
| 12/06/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/06/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/06/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference: Section 401.2, IMC 2006. 2. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems serving multiple rooms and with a capacity greater than 2,000 CFM. Reference: Section 606.1, IMC 2006. |
| 12/08/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM03263, 5870 E Broadwat Bl, # 154 Old Navy 1. Provide a 2006 IECC Lighting Budget Calculation, Com Check ok. 2. Sheet E1.0, shows RTU-3 on circuit HV-7,9,11, the panel schedule shows RTU-3 oncircuit 13,15,17. Ray T Majuta, PDSD, City of Tucson, Elect Pln Ck, 12/08/10 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/23/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 12/23/2010 | SUE REEVES | REJECT SHELF | Completed |