Permit Number: T10CM03251
Parcel: 12809004B

Address:
5350 E 16TH ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T10CM03251
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2011 ANDREW CONNOR LANDSCAPE REVIEW Passed
01/05/2011 ANDREW CONNOR NPPO REVIEW Passed
01/20/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide and identify accessible seating in the new canopy area seating as required by 2006 IBC, Section 1108.2 and the ICC (ANSI 117.1), Section 802.
2. Please provide structural calculations for the 8' wrought iron fence and gates.
END OF REVIEW
12/30/2010 JASON GREEN ENGINEERING REVIEW Approved
12/30/2010 MARTIN BROWN FIRE REVIEW Denied Per 2006 IFC, section 1008.1.8.4, bolts on double gate (detail SD04-A1) not permitted.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2011 CPIERCE1 OUT TO CUSTOMER Completed
02/09/2011 SUE REEVES REJECT SHELF Completed