Permit Number: T10CM03243
Parcel: 11711076A

Address:
126 E ALAMEDA ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03243
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project: T10CM03243
126 E Alamedia St
AT&T Bldg Remodel


Electrical plans denied for the following:

1. Panel schedule for Panel DP-LE-09G, indicates this is a new panel, provide information on where it is fed from, and provide conductor and cunduit sizes on feeder which feed it. Provide the load calculation concerning the equipment it feeds from.
2. Sheet E3.4, describes a piece of equipment being installed new, please provide an information sheet on it. This is the 480 V 3PH, Liebert CW114U CRAH Unit.

Ray Majuta,
Elect Pln Ck,
PDSD, City of Tucson,
11/20/10