| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Project: T10CM03243 126 E Alamedia St AT&T Bldg Remodel Electrical plans denied for the following: 1. Panel schedule for Panel DP-LE-09G, indicates this is a new panel, provide information on where it is fed from, and provide conductor and cunduit sizes on feeder which feed it. Provide the load calculation concerning the equipment it feeds from. 2. Sheet E3.4, describes a piece of equipment being installed new, please provide an information sheet on it. This is the 480 V 3PH, Liebert CW114U CRAH Unit. Ray Majuta, Elect Pln Ck, PDSD, City of Tucson, 11/20/10 Ray.Majuta@tucsonaz.gov |