Permit Number: T10CM03232
Parcel: 10610015A

Address:
3655 N ROMERO RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T10CM03232
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide complete engineered plumbing drawings.
2. Please provide a High/Low water dispenser
3. Break Room sink must be 34" a.f.f.
4. Provide wall mounted HVAC unit bracket details and structural calculations.
5. Minimum lettering size is 3/32" upper and/or lower case.
END OF REVIEW
02/14/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Denied NO PLUMBING PAGES PROVIDED.
02/14/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03232,
3655 N Romero Rd.

1. The outdoor HVAC units require Maintenance receptacles, per 2005 NEC-210.63.
2. The exhaust fans in restrooms are required to be energized when ever air transfered into them, per Mechcanical Code, see Mech remarks.

Ray Majuta,
PDSD, City of Tucson,
Elect Pln Ck,
2/14/11,
520-837-4988
02/14/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/14/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied 1) THE SEQUENCE OF OPERATION FOR THE RESTROOM EXHAUSTS PP M4.1 DOES NOT COMPLY WITH 2006 IMC 501.3. EXHAUST FANS MUST OPERATE WHEN EVER AC UNIT IS SUPPLYING AIR TO RESTROOM.

2) PLEASE PROVIDE STRUCTURAL MOUNTING DETAILS FOR WALL MOUNTED HEAT-PUMPS.
02/14/2011 RONALD BROWN ADA REVIEW Completed
02/15/2011 DROBEY1 ZONING REVIEW Needs Review
02/15/2011 DROBEY1 FIRE REVIEW Needs Review
02/15/2011 DROBEY1 WATER REVIEW Needs Review
02/15/2011 DROBEY1 ENGINEERING REVIEW Needs Review
02/15/2011 DROBEY1 WWM REVIEW Needs Review