| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide complete engineered plumbing drawings. 2. Please provide a High/Low water dispenser 3. Break Room sink must be 34" a.f.f. 4. Provide wall mounted HVAC unit bracket details and structural calculations. 5. Minimum lettering size is 3/32" upper and/or lower case. END OF REVIEW |
| 02/14/2011 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Denied | NO PLUMBING PAGES PROVIDED. |
| 02/14/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM03232, 3655 N Romero Rd. 1. The outdoor HVAC units require Maintenance receptacles, per 2005 NEC-210.63. 2. The exhaust fans in restrooms are required to be energized when ever air transfered into them, per Mechcanical Code, see Mech remarks. Ray Majuta, PDSD, City of Tucson, Elect Pln Ck, 2/14/11, 520-837-4988 |
| 02/14/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/14/2011 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1) THE SEQUENCE OF OPERATION FOR THE RESTROOM EXHAUSTS PP M4.1 DOES NOT COMPLY WITH 2006 IMC 501.3. EXHAUST FANS MUST OPERATE WHEN EVER AC UNIT IS SUPPLYING AIR TO RESTROOM. 2) PLEASE PROVIDE STRUCTURAL MOUNTING DETAILS FOR WALL MOUNTED HEAT-PUMPS. |
| 02/14/2011 | RONALD BROWN | ADA | REVIEW | Completed | |
| 02/15/2011 | DROBEY1 | ZONING | REVIEW | Needs Review | |