Permit Number: T10CM03224
Parcel: 112030710

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T10CM03224
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 1-11-11
Activity: T10CM03224
Address: 2917 E Richards Row
Applicant: Jaca Design LLC

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings and one set of the first submission for reference. All corrections and revisions shall be made on original tracings or finished reproducible set. Pencil and/or white out on final prints will not be acceptable. To expedite review, please cloud the originally submitted set with red ink and limit clouding on final set. Ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

PLUMBING PLAN:
2. Size the gas supply piping sufficient for the proposed demand, UPC 1217.0 Table 12-8.
3. Provide the maximum developed length of water line from the meter the furthest appliance served, UPC Table 6-6.

ELECTRICAL PLAN:
4. Bathroom receptacles are not permitted to share a circuit with receptacles in other areas, E3603.4.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review