Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM03203
Parcel: 126180130

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03203
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T10CM03203 R1
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
" Provide a consistent system layout plan and three line diagram showing the proposed type and number of collector panels. The layout shows 24 panels. The diagram shows 12 Suntech STP170S panels. The spec sheet is for Yingli YL 235 P panels.

NOTES / SPECIFICATIONS
1. Provide the exact wording and location for the Power Source "Imp, Vmp, Vmax, Isc" marking required by NEC 690.53.
2. Show the "backfed" label at the service panel circuit breaker in compliance with NEC 690.64 (B) (5).

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2011 DELMA ROBEY OUT TO CUSTOMER Completed