Review Details: COMMERCIAL - TI

Permit Number - T10CM03172
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2010 STEVE SHIELDS ZONING REVIEW Approved
11/10/2010 PAUL MACHADO ENGINEERING REVIEW Approved
11/12/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PP E-3, ONE LINE HAS NEW TRANSFORMER BEING FED WITH 4 #8 CONDUCTORS WHICH ARE PROTECTED AT 125 AMP PER PANEL SCHEDULE ON PP E-2. PLEASE ADJUST

COMPLIANCE WITH IECC 505; CHART ON PP E1.0 DOES NOT INDICATE HOW OFFICES AND OPEN OFFICE ARE MEETING REQUIREMENTS
11/12/2010 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
11/12/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/12/2010 RMYERS1 WATER REVIEW Approved
11/12/2010 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. See detail 3 P1.1 wet vent. Refer to 908.2 2006 UPC. Each wet vented section shall be a minimum of one pipe size larger than the required minimum waste size of the upper fixture... also see table 7-5 2006 UPC minimum waste size for a sink is two inch.
11/12/2010 MARTIN BROWN FIRE REVIEW Approved
11/12/2010 ERIC NEWCOMB ADA REVIEW Passed
11/12/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/12/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
11/23/2010 CAGUILA1 WWM REVIEW Needs Review