Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T10CM03172
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/10/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
11/10/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
11/12/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PP E-3, ONE LINE HAS NEW TRANSFORMER BEING FED WITH 4 #8 CONDUCTORS WHICH ARE PROTECTED AT 125 AMP PER PANEL SCHEDULE ON PP E-2. PLEASE ADJUST COMPLIANCE WITH IECC 505; CHART ON PP E1.0 DOES NOT INDICATE HOW OFFICES AND OPEN OFFICE ARE MEETING REQUIREMENTS |
11/12/2010 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
11/12/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/12/2010 | RMYERS1 | WATER | REVIEW | Approved | |
11/12/2010 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. See detail 3 P1.1 wet vent. Refer to 908.2 2006 UPC. Each wet vented section shall be a minimum of one pipe size larger than the required minimum waste size of the upper fixture... also see table 7-5 2006 UPC minimum waste size for a sink is two inch. |
11/12/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/12/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
11/12/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/12/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
11/23/2010 | CAGUILA1 | WWM | REVIEW | Needs Review |