Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM03132
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/14/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/21/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. The electrical mechanical and plumbing plans do not match the architectural. Please reconcile. a. Coordinate required exit doors b. Show the new 1 hour rated corridor walls. 2. The South exit door must swing out with an exit occupant load of 50 or more as pet the 2006 IBC, Section 1008.1.2. 3. Please provide a weight analysis between the existing HVAC units being replaced and the new HVAC units. If the new units are more weight than the existing one, please provide a complete structural analysis by a structural engineer. 4. Your appeal has been accepted and is in the review process. An additional fee of $132.00 has been added to your permit account. END OF REVIEW |
| 01/25/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) Panel A has a circuit for HP-6 which is not sized. 2) HP-7 circuitry is not in panel schedules. 3) Exhaust fans 1,2,3 are not indicated in power plans nor panel schedules. Also there is no switching indicated for these fans nor other wiring details for sequence of operation with HP-4. 4) Please provide an Energy compliance certificate. 5) Plans for roof-top A/C units to be incorporated into plan set. (there are currently two pp E3.0, to incorporate plans from EDA that sheet needs to be re-numbered and added into set) |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/02/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 02/02/2011 | SUE REEVES | REJECT SHELF | Completed |