Permit Number: T10CM03132
Parcel: 11713037A

Address:
57 E JACKSON ST

Review Status: Completed

Review Details: OTHER

Permit Number - T10CM03132
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: IN ADDITION TO THE 19 REVIEW COMMENTS PROVIDED BY RONALD BROWN ON 11-16-2010, ADD THE FOLLOWING COMMENTS.
2. SHEET A1; WEST EXTERIOR WALL: NOTES ON THE WEST WALL INDICATE A ONE HOUR FIRE RATED WALL AND A NEW 20 MINUTE FIRE RATED DOOR. FIRE WALL RATING REQUIREMENTS MUST MEET IBC SECTION 705 CRITERIA FOR FIRE WALLS, AND IBC TABLE 715.4 FOR FIRE DOORS. REVIEW AND REVISE.
3. SHEET A1; EAST EXTERIOR WALLS: AT THE EXISTING PASS THROUGH, PROVIDE THE FIRE RATINGS OF THE EXISTING BUILDING WALLS AND EXISTING DOORS (FOR BOTH BUILDINGS) ON THE PLANS. PROVIDE THE FIRE RATING OF THE GLASS BLOCK.
4. PREVIOUS COMMENT: IT WILL BE NECESSARY TO APPEAL THE BUILDING OFFICIAL AS TO HOW THE THREE SEPARATE PROPERTIES CONNECT AND THEIR USE OF A COMMON MEANS OF EGRESS.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2010 CPIERCE1 OUT TO CUSTOMER Completed