Permit Number: T10CM03132
Parcel: 11713037A

Address:
57 E JACKSON ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03132
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Resubmittal Comments from Eric Newcomb Review
1. ok
2. ok
3. PROVIDE AN OCCUPANCY LOAD FOR THE MEETING ROOM, INDICATING IF TWO EXITS ARE REQUIRED.
This occupancy load must be included for the total building occupancy load. Two exits are required.

4. Ok for the service sink but why didn't you also show the water heater next to it?

5. Ok.
6. Ok
7. SHOW ALL DOORS AND INDICATE THE DOOR SWING.
a. Please coordinate all doors and swings shown on both the Site Plan, Sheet C1 and Floor Plan, Sheet A1

8. Ok

9. Ok for the door lintel but what about load calculations and connection detils for all the new roof top mounted HVAC units?

10. Ok

ADDITIONAL REVIEW COMMENTS BY Ron Brown
11. Provide structyural details and calculations for the new roof top mounted HVAC units.
12. Please show the existing conditions and demolition scope of work on a separate Existing/Demolition Floor Plan.
13. On Sheet A1, please identify (show a graphic denstiction) between the new building elements and existing building elements to remain.
14. Please provide large scale partial plans and details of all three reamps and the two stairs showing all accessible dimensions and required grab bars. Show compliance with the 2006 IBC, Chapter 11, Sections 1012, 1009 and ICC (ANSI 117.1), Sections 504 and 505.
15. Prrovide a complete Building Code Data analysis and include on drawings.
a. Show proper occupancy load calculations. Include meeting room occupants.
b. State if building is sprinkelered or not
16. Provide complete door schedule with hardward sets defined.
17. Provide large scale tiolet floor plans and interior elevations.
a. Generic accessible details are not acceptable. Provide all accessible dimensions and accessories on the actual designed large scale toilet room elevations.
b. Provide wainscote asc per 1006 IBC, Section 1210.2.
18. Any work done in the area called called "Future Tenant Improvement" is to have a separate building permit.
19. Sheet A1 indicates a structural detail for the westerly exit door. No such detail is provided on the drawigs.
END OF RESUBMITTAL REVIEW
11/16/2010 RONALD BROWN ZONING HC REVIEW Denied REFERENCE BUILDING COMMENTS
11/18/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Replot sheet P1.1 so that the background is legible. Reference: Section 103.2.3, UPC 2006.
2. Comment not resolved; the branch piping is now called out as both ¾" and 1" - clarify the size. The branch piping size called out for the urinal flush valve will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
11/18/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Replot sheets DM1 and M1.1 so that the background is legible. Reference: Section 106.3.1, IMC 2006.
11/24/2010 GERRY KOZIOL WWM REVIEW Approved
11/30/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied DISCONNECT SIZES IN ELECTRICAL FEEDER SCHEDULE PP E3.0 DO NOT CORRESPOND WITH PANEL SCHEDULES.

PLEASE JUSTIFY FEEDER SIZES FOR NOTED DISCONNECTS IN ELECTRICAL FEEDER SCHEDULE.

PLEASE CLARIFY IF CIRUIT L1-31 IS BEING USED FOR LIGHTING AND EXHAUST FANS . PLEASE INDICATE SIZE & SEQUENCING OF EXHAUST FANS FOR COMPLIANCE WITH THE 2006 IMC.

HOW IS BATHROOM LIGHTING SWITCHED?

PLEASE COORDINATE UNDERLYING FLOOR PLAN WITH ARCHITECTURAL PAGES (DO NOT SHOW "GRAYED IN" USES THAT ARE NOT SHOWN ON ARCHITECTURAL PAGES)

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2010 CPIERCE1 OUT TO CUSTOMER Completed
12/08/2010 SUE REEVES REJECT SHELF Completed