Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T10CM03132
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/08/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 11/08/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Replot sheets DM1 and M1.1 so that the background is legible. Reference: Section 103.2.3, UPC 2006. |
| 11/08/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/08/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/08/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. A SITE PLAN INDICATING ALL THREE OF THE STRUCTURES AND HOW THEY ARE CONNECTED FOR EXITING IS REQUIRED. 2. IT WILL BE NECESSARY TO APPEAL THE BUILDING OFFICIAL FOR THIS PROJECT IN RELATION TO HOW THE THREE SEPARATE BUILDINGS CONNECT AND USE A COMMON MEANS OF EGRESS. 3. PROVIDE AN OCCUPANCY LOAD FOR THE MEETING ROOM, INDICATING IF TWO EXITS ARE REQUIRED. 4. INDICATE THE SERVICE SINK ON THE ARCHITECTURAL PLAN. 5. INDICATE THE HIGH/LOW DRINKING FOUNTAIN, OR SINGLE POINT-OF-USE WATER COOLER, ON THE ARCHITECTURAL PLAN. 6. INDICATE FIRE RATED WALLS ON THE ARCHITECTURAL PLAN AT THE FIRE CORRIDOR. 7. SHOW ALL DOORS AND INDICATE THE DOOR SWING. 8. INDICATE TRAVEL DISTANCES ON THE PLANS, MAKING SURE THESE DISTANCES MEET IBC CODE REQUIREMENTS. 9. PROVIDE STRUCTURAL CALCULATIONS AND DETAILS FOR THE NEW DOOR OPENING IN THE EXISTING WALL (THIS WAS AN OPENING THAT WAS NOT PERMITTED). 10. PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 11/08/2010 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 11/08/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Replot sheet P1.1 so that the background is legible. Reference: Section 103.2.3, UPC 2006. 2. The branch piping size called out for the urinal flush valve will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6. 3. Verify the size of the wet vent between the urinal and the water closet. The size of a wet vent shall be a minimum of one pipe size greater than that required for the drain of the upper fixture. Reference: Section 908.2, UPC 2006. 4. Provide listing information for the backing material specified in detail 1/M9.2. |
| 11/08/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 11/08/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/08/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 11/08/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/08/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/08/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |