Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2010 TERRY STEVENS ZONING REVIEW Approved
11/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Replot sheets DM1 and M1.1 so that the background is legible. Reference: Section 103.2.3, UPC 2006.
11/08/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/08/2010 ROBERT SHERRY WATER REVIEW Approved
11/08/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. A SITE PLAN INDICATING ALL THREE OF THE STRUCTURES AND HOW THEY ARE CONNECTED FOR EXITING IS REQUIRED.
2. IT WILL BE NECESSARY TO APPEAL THE BUILDING OFFICIAL FOR THIS PROJECT IN RELATION TO HOW THE THREE SEPARATE BUILDINGS CONNECT AND USE A COMMON MEANS OF EGRESS.
3. PROVIDE AN OCCUPANCY LOAD FOR THE MEETING ROOM, INDICATING IF TWO EXITS ARE REQUIRED.
4. INDICATE THE SERVICE SINK ON THE ARCHITECTURAL PLAN.
5. INDICATE THE HIGH/LOW DRINKING FOUNTAIN, OR SINGLE POINT-OF-USE WATER COOLER, ON THE ARCHITECTURAL PLAN.
6. INDICATE FIRE RATED WALLS ON THE ARCHITECTURAL PLAN AT THE FIRE CORRIDOR.
7. SHOW ALL DOORS AND INDICATE THE DOOR SWING.
8. INDICATE TRAVEL DISTANCES ON THE PLANS, MAKING SURE THESE DISTANCES MEET IBC CODE REQUIREMENTS.
9. PROVIDE STRUCTURAL CALCULATIONS AND DETAILS FOR THE NEW DOOR OPENING IN THE EXISTING WALL (THIS WAS AN OPENING THAT WAS NOT PERMITTED).
10. PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/08/2010 DROBEY1 WWM REVIEW Needs Review
11/08/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Replot sheet P1.1 so that the background is legible. Reference: Section 103.2.3, UPC 2006.
2. The branch piping size called out for the urinal flush valve will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
3. Verify the size of the wet vent between the urinal and the water closet. The size of a wet vent shall be a minimum of one pipe size greater than that required for the drain of the upper fixture. Reference: Section 908.2, UPC 2006.
4. Provide listing information for the backing material specified in detail 1/M9.2.
11/08/2010 PAUL MACHADO ENGINEERING REVIEW Approved
11/08/2010 MARTIN BROWN FIRE REVIEW Approved
11/08/2010 ERIC NEWCOMB ADA REVIEW Passed
11/08/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/08/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2010 DELMA ROBEY OUT TO CUSTOMER Completed