Permit Number: T10CM03124
Parcel: 11450004K

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T10CM03124
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2010 DAVE MANN FIRE REVIEW Approved
11/24/2010 LOREN MAKUS ENGINEERING REVIEW Approved November 29, 2010

The applicant is authorized to use a portion of the flood hazard area (FEMA Zone AE, Panel 1665) in the City of Tucson, Arizona, on the property described as 8300 East Tanque Verde Road for the purpose of installing a solar photovoltaic system.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard regulations, and is particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations require the issuance of an additional Floodplain Use Permit.

The following conditions shall apply to this permit.

1. All work shall conform to the approved improvement plans which are made part of this permit (T10CM03124) which is for installation of a supplemental photovoltaic system.

2. The existing structure is a conforming structure (FUP T04OT01507). The system attached to the existing will be at or above the existing finish floor elevation. The detached elements of the photovoltaic system will be constructed to minimize flood damage potential.

3. Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

4. Any additional improvements not reflected in the current permit will be subject to separate review and additional permits.

5. This permit becomes invalid and is subject to additional floodplain review, if any required improvement permit(s') changes the configuration of the structure and or site development.

This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit.
The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
11/29/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. The drawings showing the roof top mounted PV system specifys a mounting bracket (3 per skid) attached to the standing seam of the metal roof with two gasketed sheet metal screws on either side of the bracket. The PV framing is then bolted to these brackets.
a. Please oprovide a complete structural analysis by a certified structural engineer.
b. The civil engineer on this project, Mr. William Gilbert has analyized the existing roof trusses as beening adequate for the additional roof load and wind up-lift of the PV panels. He has also recommended the solar panels be installed with 5/16" lag screws embedded into the top cord of the existing pre-manufactured wood trusses. This is not relative to the standing seam bracket installation. Please reconsile.
c. Please coordinate the metal roofing warrantee with the roofing manufacturer.
11/30/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/30/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/01/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM03124,
8300 E Tanque Verde,
46,980 Watt DC Photovoltaic System

The electrical plans have been denied for the following:

1.City of Tucson Submittal Requirements state all plans must be legible, with a minimum text size of at least 3/32'' all uppercase. Some sheets ok some too small.Please enlarge text size and resubmit.

Ray T Majuta,
Elect Plan Ck,
PDSD, City of Tucson,
12/02/10,