Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T10CM03111
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/09/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/09/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/09/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/09/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/09/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 03/09/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/09/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved |