Permit Number: T10CM03109
Parcel: 129020010

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03109
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2010 MARTIN BROWN FIRE REVIEW Denied Per section 903.2.6, M occupancy over 12,000 sq. ft. requires fire sprinklers. Any additions allow a new look at code compliance. If occupancy classification remains Mercantile, compliance could be achieved utilizing 2 hour fire wall separation to reduce square foot. If occupancy changes to A-2(restaurant), any occupant over 100 will require fire sprinklers.
11/30/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide all Special Inspection Certifications.
2. At sheet S3.1 the two new beams at the bar joist area are listed in the calculations as HSS 12 x 4 x 1/4. The drawings have them scheduled as B2, 6 x 6. Please reconcile.
3. The Building Code Analysis Data chart on sheet A0.0 list the building occupancy as "M" for mercantile while the floor plan is clearly for a restaurant A-2. Please reconcile.
4. As a restaurant use the approximate occupancy load is over 100. As per 2006 IBC, Section 903.2.1.2 (2) a sprinkler system is required. Please reference the Fire folder for additional sprinkler requirements.
END OF REVIEW
12/02/2010 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 3048 E. Broadway Blvd.
T10CM03109
Building Plan (1st Review)

TRANSMITTAL DATE: December 2, 2010

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. As an expansion of building area is proposed a site plan review is required.

3. Provide a copy of the approved site plan showing the area of expansion.

4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t10cm03109.doc

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2010 CPIERCE1 OUT TO CUSTOMER Completed
12/02/2010 SUE REEVES REJECT SHELF Completed