Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical Revision denied due to following:

1. The Service was shown as an underground fed on the previous plan, this plan shows the service fed overhead. The City of Tucson requires all services to be underground unless a waiver is approved through the Building Official first. Was not notified of this change previously.
2. Only Sheet E-5 was submitted for a revision which deleted Panel C, Sheet E-1 on the not revised , still shows all the circuits still going to Panel C, they also have to be changed to show thatn they go to panel A or B, was not notified of this previously. All Sheets showing Panel C must be revised to show the elimination of panel C .

Please submit all sheets which have revisions on them showing if items have been revised or omitted.

When we discussed revisions, I was not advised of the above changes, otherwise I would have informed you.

Ray T Majuta
Elect Pln Ck,PDSD,
City of Tucson,
3/5/11,