Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM03086
Parcel: 11103016A

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T10CM03086
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2010 JASON GREEN ENGINEERING REVIEW Approved
11/09/2010 MARTIN BROWN FIRE REVIEW Approved
11/10/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/16/2010 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Approved
11/30/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PP E-1 HAS A PROPOSED PANEL WITH AN AIC RATING OF 10K WHILE 1 LINE DIAGRAM ON PP E-2 HAS A FUSED DISCONNECT WITH A RATING OF 100 AIC. PLEASE PROVIDE FAULT CURRENT CALCULATIONS TO JUSTIFY EQUIPMENT RATINGS.
11/30/2010 MICHAEL WYNEKEN PLANNING-CITY HALL REVIEW Approved
12/02/2010 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2011 SUE REEVES OUT TO CUSTOMER Completed
01/06/2011 SUE REEVES REJECT SHELF Completed