Permit Number: T10CM03081
Parcel: 133153000

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03081
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; the temperature extender (Watts model N170L) is not listed for limiting the water temperature at fixtures. Quoting the installation document for the Watts N170L, "Watts Hot Water Extender Tempering Valves cannot be used for tempering water temperature at fixtures. Severe bodily injury (i.e., scalding or chilling) and/or death may result depending upon system water pressure changes and/or supply water temperature changes. ASSE standard 1016 listed devices such as Watts Series MMV and L111 valves should be used at fixtures to prevent possible injury." Reference: Sections 310.4 and 413.1, UPC 2006 and Section 504.3, IECC 2006.
01/04/2011 GERRY KOZIOL WWM REVIEW Approved
01/05/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/23/2010 ERIC NEWCOMB ZONE H/C REVIEW Approved 1. SEE BUILDING COMMENTS.
12/23/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. SEE PREVIOUS COMMENT 1. APPEAL TO THE BUILDING OFFICIAL WAS DENIED. REVISE THE FLOOR PLAN ON SHEET A-2.1 TO MEET THE MANEUVERING CLEARANCE OF 18" MINIMUM FOR THE FRONT APPROACH ON THE PULL SIDE OF THE DOOR PER ICC/ANSI A117.1-2003 FIGURE 404.2.3.1(a).
2. SEE PREVIOUS COMMENT 2. APPEAL TO THE BUILDING OFFICIAL WAS DENIED. REVISE THE FLOOR PLAN ON SHEET D-2 TO MEET THE MANEUVERING CLEARANCE OF 18" MINIMUM FOR THE FRONT APPROACH ON THE PULL SIDE OF THE DOOR PER ICC/ANSI A117.1-2003 FIGURE 404.2.3.1(a).

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/06/2011 SUE REEVES REJECT SHELF Completed