Permit Number: T10CM03081
Parcel: 133153000

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03081
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2010 DAVE MANN FIRE REVIEW Approved
11/09/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-2.1; FLOOR PLAN: IN THE MEN'S AND WOMEN'S RESTROOMS, A MANEUVERING CLEARANCE OF 18" MINIMUM IS REQUIRED FOR THE FRONT APPROACH ON THE PULL SIDE OF THE DOOR PER ICC/ANSI A117.1-2003 FIGURE 404.2.3.1(a). VERIFY.
2. SHEET D-2; TOILET ROOM PLAN: SEE NOTE 1.
3. SHEET D-3; SECTION 9: ADDRESS THE CONNECTION OF THE CANOPY TO THE WALL (PROVIDE THE SIZE, QUANTITY, AND SPACING OF THE ANCHORS, OR "PER MANUFACTURER") .
4. SHEET D-3; SECTION 12: THE BLOCKING INDICATED ON THE SECTION DOES NOT MATCH THE BLOCKING ON THE ENLARGED DETAIL. VERIFY.
5. SHEET D-3; SECTION 12: ADDRESS THE CONNECTION OF THE CANOPY TO THE WALL (PROVIDE THE SIZE, QUANTITY, AND SPACING OF THE ANCHORS, OR "PER MANUFACTURER").
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/10/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
11/17/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water supply to the public lavatories is to be controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. Show how the drainage piping is to be "adapted" for the new location of the lavatories. Reference: Section 103.2.3, UPC 2006.
11/17/2010 ROBERT SHERRY WATER REVIEW Approved
11/17/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/23/2010 GERRY KOZIOL WWM REVIEW Denied need to provide complete plumbing fixture schedule to include the total # of all fixtures connected to the sanitary sewer system (including all drains) with waste pipe sizes. provide plumbing plan with grease trap/interceptor and calclations.
need evaluation for connection fee credits by WW Maps & Records- 5th floor PWB- 740-6606
11/29/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT: T10CM03081
6872 E TANQUE VERDE RD
KFC REMODEL
1. What are the the new fixtures shown on sheet A-3 being connected to ?

Ray T Majuta,
PDSD,City of Tucson,
Elect Pln Ck,
11/30/10
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2010 CPIERCE1 OUT TO CUSTOMER Completed
12/02/2010 SUE REEVES REJECT SHELF Completed