The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM03062
Parcel: 13323093C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T10CM03062
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/01/2010 TERRY STEVENS ZONING REVIEW Passed
11/01/2010 LOREN MAKUS ENGINEERING REVIEW Approved
11/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Commercial projects require drawings sealed by an Arizona registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide an expansion tank for the closed-loop heating system. Reference: Section 608.3, UPC 2006.
3. Provide a double-walled heat exchanger for the solar water heaters. Reference: Section 603.4.4.1, UPC 2006.