| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/01/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/01/2010 | TERRY STEVENS | ZONING | REVIEW | Passed | |
| 11/01/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/01/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Commercial projects require drawings sealed by an Arizona registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide an expansion tank for the closed-loop heating system. Reference: Section 608.3, UPC 2006. 3. Provide a double-walled heat exchanger for the solar water heaters. Reference: Section 603.4.4.1, UPC 2006. |