Permit Number: T10CM03042
Parcel: 12702266B

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T10CM03042
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2010 DAVE MANN FIRE REVIEW Approved
11/03/2010 MICHAEL WYNEKEN PLANNING-CITY HALL REVIEW Denied There is no record of receiving the 207 Waiver as required in Zoning Examiner condition 2. The fully executed original waiver document should be delivered directly to Michael Wyneken, with a copy attached to the ZE decision letter in the next submittal.

The Pole details and elevations page contains a note stating the antennas will be painted to match the pole. Per condition 11, the antennas are to be painted to match the fronds. The note must be changed.
11/04/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide the Equipment Shelter pad and foundation structural calculations.
2. Please provide Special Inspection Certifications as required by 2006 IBC, Sections 106 and 1702. A list of inspections has been added to the conditions menu of this permit application. Please review and provide any changes in writing.
END OF REVIEW
11/17/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T10CM03042
5336 E. Speedway Blvd. (1st Review)

TRANSMITTAL DATE: November 17, 2010

1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The plan must be approved and stamped by the Special Exception Section prior to approval by Zoning.

3. Provide the recordation information, docket and page, for the "12' WIDE ACCESS EASEMENT" shown on the site plan.

4. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the approved Special Exception process. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\celltower\t10cm03042.doc
11/23/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
11/23/2010 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/15/2010 CPIERCE1 OUT TO CUSTOMER Completed
12/15/2010 SUE REEVES REJECT SHELF Completed