Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T10CM03021
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
" Provide consistent plans showing the number of solar panels. Sheet #2 notates 4 strings of 11 modules and the line diagram shows 10 modules each array.
" Provide manufacturer specification sheets for the inverter and mounting hardware.

STRUCTURAL PLANS:
1. Provide complete roof framing information for determining load carrying capacity of each structure supporting a collector group. Show size, spacing and span of all framing members including rafters and any beams, R301.1.
DIAGRAMS / CALCULATIONS
1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1.
NOTES / SPECIFICATIONS
1. Provide the location for the "backfed" circuit breaker in compliance with NEC 690.64 (B) (5).
2. Specify that all equipment shall be listed by an Independent Testing Agency.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/05/2010 CPIERCE1 OUT TO CUSTOMER Completed
11/05/2010 SUE REEVES REJECT SHELF Completed