Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02995
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/27/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
10/27/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The hallway may not be used as a return duct. 2. Condensate drain may not directly connect to the lavatory tailpiece if the lavatory is not in the area controlling the thermostat. 3. Correct the outside air calculations. 4. State the minimum R-value for the ductwork. 5. Add balancing data. 6. Minimum font size is 3/32" |
10/27/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/27/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/27/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/27/2010 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
10/27/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
10/27/2010 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
10/27/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/27/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
10/28/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/28/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/28/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |