Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02995
Parcel: 12809006B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02995
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2010 TERRY STEVENS ZONING REVIEW Approved
10/27/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The hallway may not be used as a return duct.
2. Condensate drain may not directly connect to the lavatory tailpiece if the lavatory is not in the area controlling the thermostat.
3. Correct the outside air calculations.
4. State the minimum R-value for the ductwork.
5. Add balancing data.
6. Minimum font size is 3/32"
10/27/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/27/2010 ROBERT SHERRY WATER REVIEW Approved
10/27/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/27/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
10/27/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/27/2010 JASON GREEN ENGINEERING REVIEW Approved
10/27/2010 MARTIN BROWN FIRE REVIEW Approved
10/27/2010 ERIC NEWCOMB ADA REVIEW Passed
10/28/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/28/2010 RONALD BROWN ZONING HC REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/28/2010 SUE REEVES OUT TO CUSTOMER Completed