Permit Number - T10CM02983
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/17/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Include all fixtures when calculating the total demand and use the fixture units shown in Table A-2 (Assembly), UPC 2006. Diversity is already included in the fixture unit calculations. In addition, this system appears to consist of flush valve demand. Reference: Section 610.1, UPC 2006. 2. Tucson Water limits a 2" meter to a maximum demand of 80 GPM. Provide a letter from Tucson Water confirming that the use of a 2" water meter will be allowed for this project (172.5 flush valve fixture units equals 85 GPM). Reference: Sections 610.2 and 610.12, UPC 2006 |
| 11/18/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/18/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |