| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 01/18/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; the appropriate classification for the dining areas is "Cafeteria/fast food dining" at 100 people per 1,000 square feet and 9 CFM per person, not "Restaurant dining rooms" at 70 people per 1,000 square feet and 10 CFM per person. Revise the calculations for RTU-3 and RTU-4 as required. [Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used. Revise the calculations for RTU-3 and RTU-4 using the default occupant densities. Reference: Section 401.2, IMC 2006.] |
| 01/19/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a reduced pressure zone backflow prevention assembly for the carbonator. Provide individual backflow protection devices for the bun steamer and the specialty coffee machine. Reference: Sections 602.2 and 603.4.12, UPC 2006. [Appliances (e.g. steamers, ice makers, coffee makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Each piece of equipment requiring backflow protection shall be independently protected. Reference: Sections 602.2 and 603.0, UPC 2006, as amended by the City of Tucson.] 2. Comment not resolved; no water pressure or water pipe sizing calculations were shown on the drawings or included in the submittal. [Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006.] 3. Comment not resolved; notes #4 and #5 quote the IPC but do not comply with the requirements of the UPC. [Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.] 4. Comment not resolved; no notes on sheet P4.0 address the required cleanout sizes. [Provide cleanouts sized per Section 707.11, UPC 2006.] 5. Comment not resolved; notes #3 and #10 have not been changed to reflect the slope requirements of the UPC. [Revise the slope of the horizontal drainage piping to comply with the requirements of Section 708.0, UPC 2006 (see #3 and #10, Sanitary and Vent Systems, General Plumbing Notes).] 6. Comment not resolved; detail 1 on sheet P3.0 still shows two GT-1500 gravity grease interceptors being installed as does the interceptor schedule on sheet P4.1. The utility plan, UT01, is basically correct but does not show the vents for the grease separators. [Provide listing information to show that the specified gravity grease interceptor (Green Turtle 1500 (2)) complies with the requirements of Section 1014.3.3.1, UPC 2006. Note that the proposed gravity grease interceptor has a 6" inlet and outlet but the site plan indicates a 4" building sewer downstream of the interceptor.] 7. Revision "B" to the plumbing fixture schedule on sheet P4.1 calls for the lavatory faucets to have a water use of "1.0 GPM (1.06 GAL/60 SEC CYCLE". According to ARS Title 45, Chapter 1, Article 12 (See text at: http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp), the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. In addition, accessible metering faucets shall remain open for a minimum of 10 seconds. Reference: Section 402.1, UPC 2006, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-2003. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/01/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 02/01/2011 | SUE REEVES | REJECT SHELF | Completed |