Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T10CM02976
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/19/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | DDO required. See previous comments. Pick up the plans for the DDO submittal after notice of approval from Michael Taku. |
| 12/03/2010 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | T10CM02976 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. STRUCTURAL PLANS: 1. Notate or detail the beam-end connections from the beam bearing point to the foundation for verifying carrying capacity (Detail 1/A-01 or Section A-A), R301.1. PLUMBING PLANS: 1. Show an individual water heater for each building, P2801. MECHANICAL PLANS: 1. Provide heating facilities in all habitable rooms (living/bedroom), R303.8. ELECTRICAL PLANS: 1. Provide a feeder load calculation for the new sub-panel as shown at Table E3604.2(1). Account for existing, space heating and water heating demands. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/07/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 12/07/2010 | SUE REEVES | REJECT SHELF | Completed |