Permit Number: T10CM02972
Parcel: 12704001B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02972
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2010 MARTIN BROWN FIRE REVIEW Approved
10/29/2010 BEV HESTER ENGINEERING REVIEW Denied The building permit will be approved when the floodplain use permit is approved.
11/02/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved For Eric
11/03/2010 RMYERS1 WATER REVIEW Approved
11/03/2010 RICK MYERS PLUMBING-COMMERCIAL REVIEW Approved 1. The City of Tucson is currently using the 2006 UPC.
11/09/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the size of the proposed grease duct to provide a minimum velocity of 1500 feet per minute. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson.
2. Revise the installation of the hood to provide 18" of clearance between the hood and combustible construction (Note that wood studs covered by gypsum board and a sheet of stainless steel are considered combustible construction by the IMC. FRP wall covering within 18" of the hood is also combustible construction.). Reference: Section 507.9, IMC 2006.
3. CaptiveAire literature requires that HVAC diffusers be located at least ten feet from the hood to prevent possible disruption of the hood capture and containment. Reference: Sections 304.1 and 507.16, IMC 2006.
11/17/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied There are no electrical drawings provided for the new equipment. provide detail on how new equipment is to be wired, name any circuits which may be reused.

Ray T Majuta,
PDSD,City of Tucson,
Elect Plan Ck,
11/17/10,
Ray.Majuta@tucsonaz.gov
11/19/2010 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/16/2011 DELMA ROBEY OUT TO CUSTOMER Completed
02/16/2011 SUE REEVES REJECT SHELF Completed