Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02972
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/26/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/29/2010 | BEV HESTER | ENGINEERING | REVIEW | Denied | The building permit will be approved when the floodplain use permit is approved. |
| 11/02/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | For Eric |
| 11/03/2010 | RMYERS1 | WATER | REVIEW | Approved | |
| 11/03/2010 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Approved | 1. The City of Tucson is currently using the 2006 UPC. |
| 11/09/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the proposed grease duct to provide a minimum velocity of 1500 feet per minute. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson. 2. Revise the installation of the hood to provide 18" of clearance between the hood and combustible construction (Note that wood studs covered by gypsum board and a sheet of stainless steel are considered combustible construction by the IMC. FRP wall covering within 18" of the hood is also combustible construction.). Reference: Section 507.9, IMC 2006. 3. CaptiveAire literature requires that HVAC diffusers be located at least ten feet from the hood to prevent possible disruption of the hood capture and containment. Reference: Sections 304.1 and 507.16, IMC 2006. |
| 11/17/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | There are no electrical drawings provided for the new equipment. provide detail on how new equipment is to be wired, name any circuits which may be reused. Ray T Majuta, PDSD,City of Tucson, Elect Plan Ck, 11/17/10, Ray.Majuta@tucsonaz.gov |
| 11/19/2010 | GERRY KOZIOL | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/16/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 02/16/2011 | SUE REEVES | REJECT SHELF | Completed |