Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02964
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/29/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
12/02/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | PLEASE PROVIDE CLEAR STRUCTURAL CONSTRUCTION INFORMATION FOR ALL INTERIOR WALLS. THE MULTIPLE KEYNOTES FOR EACH WALL ON PP A3.0 ARE CONFUSING AND HAVE CONFLICTING INFORMATION AS WALL FINISH HAS BEEN COMBINED WITH WALL TYPE. COORDINATE LIGHTING DETAILS PP A4.0 WITH ELECTRICAL PAGES OR DELETE LIGHTING INFORMATION ON A4.0. DETAILS FOR BULKHEADS PP A9.1 DO NOT APPEAR TO BE USED ON THE RCP PAGE. PLEASE CLARIFY. PP S2 NOTATIONS FOR PATIO STEPS DO NOT COORDINATE WITH ARCHITECTURAL PAGES. PLEASE CLARIFY |
12/02/2010 | LEERAY HANLY | HC | REVIEW | Approved | |
12/02/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. The walls adjacent to the Type I hood are constructed with non-combustible supports and gypsum board but the tile wall covering needs further clarification. What is the extent of the tile covering (i.e. extending at least 18" beyond the hood) and how will the tile be applied so that there is no exposed, absorbent grout? Show that the installation of the three Type I hoods complies with Section 507.9, IMC 2006 for clearances (i.e. the construction of all walls within 18" of the hoods comply with the requirements of Section 507.9, IMC 2006). |
12/02/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/02/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; the appeal to the Building Official has not been approved at this time. Water-free urinals are not Code-compliant fixtures per the UPC. Submit an appeal to the Building Official requesting approval to utilize a water-free urinal based on the International Plumbing Code. Reference: Sections 211.0 (insanitary), 301.2, 405.2, 409.0, 601.1, and 1005.0, UPC 2006. 2. Comment not resolved; backflow preventers do not appear to have been specified for the three chemical dispensers. Appliances (e.g. chemical dispensers, 003. 071, and 080) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006. 3. Comment does not appear to have been addressed. Provide a vacuum relief for storage-type water heaters (i.e. WH-7) located above any fixture outlets. Reference: Section 608.7, UPC 2006. 4. Comment not resolved; the appeal to the Building Official has not been approved at this time. Permission to use a single gravity grease interceptor to serve multiple business establishments requires an appeal to the building official. Reference: sections 301.2 and 1014.3.4.3, UPC 2006. 5. Comment not resolved; the maximum capacity of a 3" building drain is 35 fixture units. The grease interceptor calculation indicates 99 fixture units being connected to the existing grease interceptor with 38 fixture units coming from the new restaurant. The maximum number of fixture units that can be accommodated by a 3" pipe is 35 fixture units. The drawing also indicates that the existing grease interceptor has a 3" inlet. This appears to be too small to accommodate the existing 61 fixture units from the existing restaurant. Reference: Section 703.2, UPC 2006. |
12/07/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED WASTEWATER CREDITS EVALUATED BY WW MAPS & RECORDS 5TH FLOOR PWB 740-6602 |
12/09/2010 | DAVID RIVERA | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/10/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
12/10/2010 | SUE REEVES | REJECT SHELF | Completed |