Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02941
Parcel: 13355231B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02941
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. The original approved drawings for the buildings did not indicate that any engineered ventilation system had been utilized; the ventilation was calculated per Section 403.3, IMC 2003. If the new work is to utilize an engineered ventilation system, provide calculations that demonstrate that the building will be adequately ventilated per the exception to Section 403.2, IMC 2006. [The new dehumidifying unit (DHU-8) does not introduce any outdoor air into the building. Show that adequate ventilation is still being supplied to the building. Reference: Sections 102.4 and 401.2, IMC 2006 and Section 403.3, IMC 2003.]
01/03/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/05/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/10/2011 GERRY KOZIOL WWM REVIEW Denied NEED CREDIT EVALUATION FOR DEMO'D FIXTURES
12/23/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/19/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/19/2011 SUE REEVES REJECT SHELF Completed