Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02941
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/03/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. The original approved drawings for the buildings did not indicate that any engineered ventilation system had been utilized; the ventilation was calculated per Section 403.3, IMC 2003. If the new work is to utilize an engineered ventilation system, provide calculations that demonstrate that the building will be adequately ventilated per the exception to Section 403.2, IMC 2006. [The new dehumidifying unit (DHU-8) does not introduce any outdoor air into the building. Show that adequate ventilation is still being supplied to the building. Reference: Sections 102.4 and 401.2, IMC 2006 and Section 403.3, IMC 2003.] |
01/03/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
01/05/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/10/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED CREDIT EVALUATION FOR DEMO'D FIXTURES |
12/23/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/19/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
01/19/2011 | SUE REEVES | REJECT SHELF | Completed |