Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM02940
Parcel: 13316013B

Address:
6500 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02940
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2010 MARTIN BROWN FIRE REVIEW Approved
10/28/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A011: THE DESIGN PROFESSIONAL DID NOT SEAL, SIGN, AND DATE THE DRAWING.
2. SHEET AD111: THE LAST LINE OF THE GENERAL CONSTRUCTION DEMOLITION NOTES CAN NOT BE READ. REVISE.
3. GENERAL: THE DESIGN PROFESSIONAL SHOULD INCLUDE THE LICENSE EXPIRATION DATE ON EACH SHEET, LOCATED NEAR THE SIGNED, DATED SEAL.
10/29/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
11/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The new dehumidifying unit (DHU-10) does not introduce any outdoor air into the building. Show that adequate ventilation is still being supplied to the building. Reference: Sections 102.4 and 401.2, IMC 2006 and Section 705 (b) 1, UBC 1991.
11/05/2010 ROBERT SHERRY WATER REVIEW Approved
11/08/2010 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1.Include a material schedule on the plan, or, provide a specification book with the plumbing and mechanical sections. 2. Refer to P351 detail two. Piping designated as "D". Include "D" in the Mechanical symbols on PMO1, and include the material type in the material schedule. 3. Refer to detail three on PMO2- all sinks require cleanouts. Refer to section 707.4 2006 UPC exception one. 4. Include how the system is to be sterilized. Refer to section 609.9 2006 UPC.
11/10/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:T10CM02940
6500 E Grant Rd
Target T-0855 TI

The electrical plans have been denied for the following:

1. Provide fault current calculations for all equipment feeding of MDS,
2. Is the main circuit breaker on Panel LP-12A intended to protect LP-12B also?

Ray Majuta,PDSD,City of Tucson,
Elect Pln Ck,
11/13/10
Ray.Majuta@tucsonaz.gov
11/19/2010 GERRY KOZIOL WWM REVIEW Approv-Cond need to provide waste line size for demoed floor sinks if you would like credits to be evaluated

Final Status

Task End Date Reviewer's Name Type of Review Description
11/23/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
11/23/2010 GERARDO BONILLA REJECT SHELF Completed