Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM02917
Parcel: 11704100A

Address:
110 E 4TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T10CM02917
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2011 GERRY KOZIOL WWM REVIEW Approved
01/24/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007. For initial construction: Effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation are required for all new SFR and duplex plans. Show the code references on the plans. Amendments to adopted codes are at the City web-site http://www.tucsonaz.gov: Planning, Building, & Business; under the Building topic; Building Ordinances and Codes; Building Codes

GENERAL NOTES:

" All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation City of Tucson Ordinance #10549 with one of the following provisions: ½"control conduit and two ¾" copper piping for water with rooftop termination; straight 3" metallic sleeve; or an accessible attic (clear path 30" wide x 30" high) over the water heater. Show appropriate notation.
" All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 with the following provisions: 1. A 4 square feet area for (meter, disconnect & inverter) equipment adjacent to the electrical service panel or near the proposed collector panel space. 2. The best roof space available for accommodating PV solar collector panels with capacity for collector dead loading (typically 4 lbs/SF). 3. A minimum 3,800 volt-ampere PV electrical load entry on the Service Load Calculation (Show as a continuous load of 15.8 A). 4. An Electrical Panel Schedule with a 240 volt circuit breaker space labeled "reserved for Photo Voltaic". Show appropriate notation.
" All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide segregated building drains for future gray water utilization, Ordinance #10579. Include both: a) dual clothes washer standpipes, one with an above grade stub-out; b) separate gray water tub/shower and lavatory drain with exterior connection to the building sewer line at 3' from foundation.

SITE PLAN:

1. Indicate the location of electric lines from property line to building, R106.1.1.

FOUNDATION PLANS:

1. Revise the Alternate Braced Wall Panel notation with a device and an installation method that provides the required 1800 LBS uplift capacity, R602.10.6. The PAHD42 is rated less than required 1800 LBS when installed with end distance less than 8". Revise the Holdown Schedule on sheet A1.1.

FLOOR PLANS:

1. Show an accessible route on the floor plan, R106.1.1. Provide a ramp between the main door and public right-of-way.

SECTIONS - DETAILS:

1. The installation of a fiber glass shingle on roof surfaces over unvented attic space may void the manufacturer's warranty. Show compliance with R806 by providing tile, metal or built-up covering, or show the shingle manufacturer's requirement on the plans.
2. Show compliance with R806.4 by stating "no vapor retarders at the ceiling" for roofs without vented attic space.

PLUMBING PLANS:

1. Provide a plumbing design using a single code, 2006 UPC or 2006 IRC. Revise the Fixture Connection Schedule (UPC) or the note references (IRC).
2. Show a provision for a future solar water system, City of Tucson Ordinance #10549.
3. Show the clothes washer drain in compliance with City of Tucson Ordinance #10579 for gray water system collection.

MECHANICAL PLANS:

1. Show a means of make-up air to the laundry closet (transfer grille, louvered or undercut door), M1307.
2. Provide return air duct size meeting minimum requirements of 72 SQ IN/ ton, M1602. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN per 1,000 BTU, M1403.1 (1 ton cooling = 12,000 BTU).

ELECTRICAL PLANS:

1. Add a double breaker space for future Photo Voltaic on the panel schedule, E3304.11 & E3606.2.
2. Show the location of a typical electrical panel on the Electrical Plan with 4 square feet of clear area for future Photo Voltaic equipment, E3501.6.2 & E3605.8.
3. Revise the electrical load calculation showing a minimum 3,800 volt-ampere or 16 Ampere 100% entry for future Photo Voltaic equipment, E3502.2.
4. Show a general description for each circuit on the panel schedule, E3304.11 & E3606.2. Include circuit #22 & 24.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/28/2011 SUE REEVES REJECT SHELF Completed