Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02914
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/01/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:T10CM02914, 13701 W Mile Wide Rd 1018.08 KW Photovoltaic System, The electrical plans have been denied for the following items, The following items have not been addressed from the last review: 1.Fault Current calculations beginning at MSD and on through to electrical equipment, not provided as requested last review. 2. Provide current caculations at following points, b. Inverter DC terminals, c. at 4 and 3 pole terminals 3. Regarding "Notes" Table Sheet 2.0, Tag #1 and #2,from last review. 4. Item #5 last review concerning use of outdoor conductors. 5. Item #6 last review concerning correction factors for modules (NEC 2005 690-7) 6. Item # 7 last review concerning NEC 690.8. Indicate how each of these were addressed. Ray T Majuta, PDSD,City of Tucson, Elect Plan Ck, 12/05/10 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/08/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 12/08/2010 | SUE REEVES | REJECT SHELF | Completed |