Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02906
Parcel: 119216450

Review Status: Active

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM02906
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T10CM02906
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

STRUCTURAL PLANS:
1. Provide complete roof framing information for determining load carrying capacity of each structure supporting a collector group. Show size, spacing and span of all framing members including trusses, joists, rafters and beams, R301.1. The design should support the dead load along with a 20 PSF live load, or show that each engineered truss receives no more than 200 pounds of additional dead loading, or provide an engineer's calculation, design and seal for verifying the truss load carrying capacity, M1401.
DIAGRAMS / CALCULATIONS
1. Maximum Photovoltaic System Voltage (Voc x 1.13) NEC 690.7. Show the appropriate factor for the low ambient temperature of 16 degrees F in Tucson.
NOTES / SPECIFICATIONS
1. Provide wire sizes between the electrical service and photovoltaic meter. The wire size chart does not include Mark 'E' on sheet #1 & 2..

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/19/2010 ANY REJECT SHELF RECEIVED