Review Details: COMMERCIAL TI
Permit Number - T10CM02887
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/18/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
10/18/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
10/18/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/18/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/18/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Architectural seal must be active and for construction 2. Provide note behind nurses counter "Employee Work Area". |
10/18/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006. 2. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. |
10/18/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/18/2010 | RONALD BROWN | ADA | REVIEW | Passed | |
10/18/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
10/28/2010 | CPIERCE1 | WWM | REVIEW | Needs Review | |
10/28/2010 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
10/28/2010 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review |