Permit Number: T10CM02887
Parcel: 119180810

Address:
3788 S 16TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02887
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2010 DAVE MANN FIRE REVIEW Approved
10/18/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
10/18/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/18/2010 ROBERT SHERRY WATER REVIEW Approved
10/18/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Architectural seal must be active and for construction
2. Provide note behind nurses counter "Employee Work Area".
10/18/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
10/18/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/18/2010 RONALD BROWN ADA REVIEW Passed
10/18/2010 RONALD BROWN ZONING HC REVIEW Approved
10/28/2010 CPIERCE1 WWM REVIEW Needs Review
10/28/2010 CPIERCE1 ZONING REVIEW Needs Review
10/28/2010 CPIERCE1 ENGINEERING REVIEW Needs Review