Permit Number: T10CM02863
Parcel: 13502001A

Address:
6420 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02863
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A 2-way cleanout is approved only at the junction of a building drain and a building sewer. Reference: Section 707.4, UPC 2006.
2. The maximum distance between cleanouts shall be 100 feet. reference: section 719.1, UPC 2006.
01/21/2011 JASON GREEN ENGINEERING REVIEW Approved
01/21/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/24/2011 CAGUILA1 WWM REVIEW Needs Review
02/24/2011 CAGUILA1 ZONING REVIEW Needs Review