Permit Number: T10CM02836
Parcel: 12901018M

Address:
191 S PLUMER AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T10CM02836
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2010 JASON GREEN ENGINEERING REVIEW Denied DATE: November 19, 2010
SUBJECT: 191 S Plumer Ave- 2nd Site/Grading Plan Engineering Review
TO: George Hayduke
LOCATION: T14S R14E Sec17 Ward 4
REVIEWERS: Jason Green, CFM
ACTIVITY: T10CM02836 (Site Plan) and T10BU01569 (Grading Plan)


SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the revised site plan (T10CM02836), grading plan (T10BU01569), Hydrologic/Hydraulic Report (Stanley Engineering & Drainage, 08OCT10, 12NOV10) and Stormwater Pollution Prevention Plan (Stanley Engineering & Drainage, 14OCT10, 14NOV10) for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. The following items need to be addressed:

DRAINAGE STATEMENT:

1) Completed.
2) Completed.
3) Completed.

SITE PLAN COMMENTS:

4) Completed.

5) Restated: DS Sec.2-02.2.1.A: Revise the site plan (or plan set since all plans have been submitted as one package) to provide a sheet index on the first page for ALL 9 Sheets submitted for site, grading, water harvesting and landscape plan review. The sheet index should include the Water Harvesting Plan and the Landscape Plan since all plan sets have been submitted under one review.

6) Completed.

7) Acknowledged: DS Sec.2-02.2.1.A: Revise the typographical error in Keynote #2 to read "Grading."

8) Completed.

9) Restated: DS Sec.2-02.2.1.A.8: Revise the site plan to clearly match the grading plan for the location of the concrete headers at the water harvesting basins within the vehicular use area. The landscape areas within the vehicular use area (VUA) must act as passive water harvesting.

10) Completed. However a new comment is to revise the parking count shown for the parking space along the east side of the property. The site plan show 7@9-foot each, however there is only 5 parking spaces shown.

11) Acknowledged: DS 2-02.2.1.A.8: However the required bicycle parking seems to have been removed from the plan set, clarify. Refer to Zoning requirements for number and location of the required bicycle parking.

12) Completed.
13) Completed.
14) Completed.
15) Completed.
16) Completed.
17) Completed.
18) Acknowledged.
19) Completed.
20) Completed.
21) Completed.
22) Completed.
23) Completed.
24) Completed.
25) Completed.
26) Completed.

GRADIN PLAN:

27) Completed.
28) Completed.
29) Completed.
30) Completed.

31) Clarify that the site plan clearly matches the grading plan for the location of the concrete headers at the water harvesting basins within the vehicular use area. The landscape areas within the vehicular use area (VUA) must act as passive water harvesting.

32) Completed.
33) Completed.
34) Completed.
35) Completed.
36) Completed.
37) Completed.
38) Completed.
39) Completed.

SWPPP COMMENTS:

40) Completed.

GENERAL COMMENTS:

Please provide a revised plan set that addresses the comment provided above. For expedite purposes the site/grading plan can be reviewed over the counter (PDSD Engineering Division comment only) for stamp approval once all items have been addressed. Please call to schedule an appointment when ready.

For questions or to schedule the appointment I can be reached at 837-4929.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Planning & Development Services
11/22/2010 ANDREW CONNOR LANDSCAPE REVIEW Approved
11/22/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Alberts Auto Care
T10CM02836
Site Plan (2nd Review)

TRANSMITTAL DATE: November 22, 2010

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the entire site.

2. As this site plan has not been approved remove all revision clouds and deltas from the plan.

3. Once the above comment has been addressed Zoning is willing to provide and over-the-counter review. Please call or email to schedule an appointment for the review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t10cm02836

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Site plan.