Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T10CM02825
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 10/22/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 10/27/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. A new Certificate of Occupancy must be issued for the entire building including the new addition. Please provide building code data for the whole building. 2. As per the 2006 IBC, Sections 106 and 1704, the engineer of record must provide a list of Special Inspections required for this project. This list is not included in the drawings. Special Inspections have been included in the Conditions Menu of this permit by the plan reviewer. Please review the selections and if some of them are not necessary, please summerize and email the list of items deleted. Please provide completed Special Inspections Certifications for review and approval. END OF REVIEW |
| 11/08/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/19/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |