Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02814
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/14/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 10/15/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Provide electrical design. |
| 10/15/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/15/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation for the restrooms per Section 403.3, IMC 2006. |
| 10/15/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/15/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. Provide an upper terminal cleanout . Reference: Section 707.4, UPC 2006. |
| 10/19/2010 | GERRY KOZIOL | WWM | REVIEW | Approved |