Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02814
Parcel: 11006017A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02814
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
10/15/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved Provide electrical design.
10/15/2010 ROBERT SHERRY WATER REVIEW Approved
10/15/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation for the restrooms per Section 403.3, IMC 2006.
10/15/2010 DAVE MANN FIRE REVIEW Approved
10/15/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. Provide an upper terminal cleanout . Reference: Section 707.4, UPC 2006.
10/19/2010 GERRY KOZIOL WWM REVIEW Approved