| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/08/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide balancing information for the two hoods, including the make-up air. |
| 10/08/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/08/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/08/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 10/08/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Directly connect the dump sink. 2. Provide a schematic diagram of the gas piping, including all loads, pipe sizes, and developed lengths. |
| 10/08/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/08/2010 | RONALD BROWN | ADA | REVIEW | Passed | |
| 10/08/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/08/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | 1. Show tray rail height between 28" to 34". 2. Show accessible seating as per Section 1108.2.2.1 |
| 10/13/2010 | CPIERCE1 | WWM | REVIEW | Needs Review |