Permit Number: T10CM02809
Parcel: 11205283F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02809
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
10/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide balancing information for the two hoods, including the make-up air.
10/08/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/08/2010 ROBERT SHERRY WATER REVIEW Approved
10/08/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/08/2010 PAUL MACHADO ENGINEERING REVIEW Approved
10/08/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Directly connect the dump sink.
2. Provide a schematic diagram of the gas piping, including all loads, pipe sizes, and developed lengths.
10/08/2010 MARTIN BROWN FIRE REVIEW Approved
10/08/2010 RONALD BROWN ADA REVIEW Passed
10/08/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/08/2010 RONALD BROWN ZONING HC REVIEW Denied 1. Show tray rail height between 28" to 34".
2. Show accessible seating as per Section 1108.2.2.1
10/13/2010 CPIERCE1 WWM REVIEW Needs Review