Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM02796
Parcel: 12801007A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02796
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A restaurant is rated as assembly occupancy; revise the Plumbing Fixture Schedule on sheet P3 accordingly. Reference: Tables 7-3 and Table A-2, UPC 2006.
2. Provide justification for the use of 3" traps for the four trench drains. Reference: Footnote 7, Table 7-3, Table 7-4, and Section 702.0, UPC 2006.
3. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area.
4. Include all of the fixtures (e.g. the four trench drains) connected to the gravity grease interceptor when determining the size of the interceptor. Resize the proposed grease interceptor per Section 1014.3.6, UPC 2006.
10/12/2010 ROBERT SHERRY WATER REVIEW Approved
10/12/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation for the prep and kitchen areas. Reference: Section 403.3, IMC 2006 as amended by the City of Tucson, and General Note 6, Table 6-1, ASHRAE Standard 62.1 - 2004.
2. "Five Guys Burgers and Fries" is a fast food restaurant; use the appropriate Occupancy Category from Table 6-1, ASHRAE Standard 62.1 - 2004 to determine the appropriate ventilation rate.
10/13/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Needs health department review
2. Provide a letter to the Building Official listing all deferred submittals for additional fee accessment.
3. Please provide Special Inspection Certification for Field Welding
END OF REVIEW
10/14/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/15/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/15/2010 RONALD BROWN HC REVIEW Denied Because this project is a change of use to a more hazardous occupancy, it is required to be a full code compliance project.
1. Please provide the last approved site plan showing all parking analysis and accessible parking spaces required as per the 2006 IBC, Table 1106.1.
2. Please show details of the actual conditions of the ramp from the Broadway right of way to the from entrance and that it complies with all accessible requirements as per ICC (ANSI 117.1), Section 405 including spot grades for slope compliance.
3. Please revise the passenger loading zone for accessible compliance as per the 2006 IBC, Section 1106.7 and ICC (ANSI 117.1), Section 503.
3. Please provide spot grades through out the entire accessible route showing compliance with 2006 IBC, ICC (ANSI 117.1), Section 403.3
4. Please provide a large scale detail of the accessible parking including the following:
a. Grades slopes as per ICC (ANSI 117.1), Section 502.5
b. Sizes of all parking spaces and aisles with dimensions for all spaces including "Van Accessible"
c. Provide 1 "Van Accessible space as per section 1106.5
d. Signage including "Van Accessible" as per 502.7
e. All required accessible parking aisles
f. Access to the accessible route in either flush condition or with a curb/sidewalk ramp as per Sections 405 and /or 406.
5. Please provide a large scale detail of the signage including "Van Accessible" signage.
6. Please confirm and insure front door accessibility as per Section 404 and 303.
7. Please confirm and insure rear exit door accessibility as per Section 404 and 303. Verify that all landings and ramps are compliant with 404, 303, 405 and 406.
END OF REVIEW
10/19/2010 GERRY KOZIOL WWM REVIEW Denied NEEDS TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER. 3RD FLOOR - CHAD A. FOR INVERT HEIGHTS AT MAIN LINE AND F.F.E. OF BUILDING ALSO NEED CAPACITY EVALUATION BY KURT STEMM 740-6534
NEEDS IWC REVIEW/APPROVAL- TOM TOMCHAK 443-6200, 5025 W INA RD

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2010 DELMA ROBEY OUT TO CUSTOMER Completed
10/26/2010 SUE REEVES REJECT SHELF Completed