Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T10CM02763
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/05/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10cm02763 4291 N Campbell Pet CT Scanning equipment The electrical plans have been denied for the following: 1. Provide Panel schedules along with load calculations for new circuits added. 2. Provide Panel schedule and total load calculation for the new 125 amp load to feed PUD from the existing RAD switchboard. Ray T Majuta, PDSD, City of Tucson, Electrical Plan Ck, 10/05/10, Ray.Majuta@tucsonaz.gov 10/27/10 Second review, the load calculations provided on a single seperate sheet need to be on the plans for the project, they are also required to have the EE's stamp, oe a delta for the change or added information. Ray T Majuta PDSD, City of Tucson Electrical Plan Ck, 10/27/10, 520-837-4988, Ray.Majuta@tucsonaz.gov |
| 10/27/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/27/2010 | CPIERCE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |