Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM02763
Parcel: 10821018X

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM02763
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need valuation
2. Provide structural analysis of suspended HVAC fan coil unit and roof top mounted compressor on existing structure
10/04/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/04/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
10/04/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the installed weight of the new mechanical equipment. Reference: Section 106.3.1, IMC 2006.
2. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
3. Provide auxiliary drain pans or secondary drain systems for the fan coil unit. Reference: Section 307.2.3 IMC 2006.
4. Materials exposed in plenums shall conform to Section 602.2.1, IMC 2006.
10/04/2010 STEVE SHIELDS ZONING REVIEW Approved
10/05/2010 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
10/05/2010 CPIERCE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/05/2010 CPIERCE1 OUT TO CUSTOMER Completed