Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T10CM02763
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/04/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Need valuation 2. Provide structural analysis of suspended HVAC fan coil unit and roof top mounted compressor on existing structure |
| 10/04/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/04/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 10/04/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the installed weight of the new mechanical equipment. Reference: Section 106.3.1, IMC 2006. 2. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. 3. Provide auxiliary drain pans or secondary drain systems for the fan coil unit. Reference: Section 307.2.3 IMC 2006. 4. Materials exposed in plenums shall conform to Section 602.2.1, IMC 2006. |
| 10/04/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/05/2010 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 10/05/2010 | CPIERCE1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/05/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |