Permit Number: T10CM02762
Parcel: 11711085A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02762
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
10/04/2010 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied PROVIDE PLAN SHOWING MECHANICAL COMPLIANCE. SUPPLY, RETURN AND BALANCING TO NEW OFFICE CUBICLES
10/04/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/04/2010 LHANLY1 WATER REVIEW Passed
10/04/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Maxium travel distance for one exit requirement as per Section 1019.2 is 75'. Actual travel distanmce is 89'.
10/04/2010 LHANLY1 WWM REVIEW Passed
10/04/2010 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed
10/04/2010 PAUL MACHADO ENGINEERING REVIEW Approved
10/04/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/04/2010 LEERAY HANLY ADA REVIEW Passed
10/04/2010 LEERAY HANLY ZONING HC REVIEW Passed SEE BUILDING REVIEW COMMENTS FOR ANY RELATED ACCESSIBILITY CORRECTIONS
11/04/2010 DAVE MANN FIRE REVIEW Approved