Permit Number: T10CM02742
Parcel: 11720029B

Address:
265 S GRANADA AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02742
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2010 MARTIN BROWN FIRE REVIEW Approved
10/14/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/14/2010 RSHERRY1 WWM REVIEW Passed No wastewater-connected fixtures.
10/14/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/14/2010 ROBERT SHERRY WATER REVIEW Approved
10/20/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/27/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02742
265 S Granada AV

The Electrical Plans have been denied for the following:

1. Sheet E604, size the grounding electrode conductor to the transformer placed at new location.
2. Sheet E605, will all 125/3 switches on MCCD have an overcurrent device of 125A ? If so the equipment grounds with the feeders should be #6.
3. Sheet E604 has a 75 kva transformer feeding a 200 amp panel with 3/0's, Sheet E701 shows PNL HW to be 60 amp with a 60 amp MCB ?
4. Sheet EP102 note to existing PNL ? Two new circuits 60 amp 2-P per note 11, and two new circuits 50 amp 2-P per note 12,describe this panel with location and panel loads.
5. Sheet EP701, where is new panel CT,where does come from ?


Ray T Majuta,PDSD,City of Tuc.,
Elect Plan CK,
10/30/10
520/837/4988

Final Status

Task End Date Reviewer's Name Type of Review Description
11/02/2010 CPIERCE1 OUT TO CUSTOMER Completed
11/02/2010 SUE REEVES REJECT SHELF Completed