Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02742
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/06/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/14/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
10/14/2010 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater-connected fixtures. |
10/14/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/14/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/20/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/27/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM02742 265 S Granada AV The Electrical Plans have been denied for the following: 1. Sheet E604, size the grounding electrode conductor to the transformer placed at new location. 2. Sheet E605, will all 125/3 switches on MCCD have an overcurrent device of 125A ? If so the equipment grounds with the feeders should be #6. 3. Sheet E604 has a 75 kva transformer feeding a 200 amp panel with 3/0's, Sheet E701 shows PNL HW to be 60 amp with a 60 amp MCB ? 4. Sheet EP102 note to existing PNL ? Two new circuits 60 amp 2-P per note 11, and two new circuits 50 amp 2-P per note 12,describe this panel with location and panel loads. 5. Sheet EP701, where is new panel CT,where does come from ? Ray T Majuta,PDSD,City of Tuc., Elect Plan CK, 10/30/10 520/837/4988 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/02/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
11/02/2010 | SUE REEVES | REJECT SHELF | Completed |